PVA: Emergency call station
The emergency call station has a gooseneck microphone with pop shield and permanent monitoring, a total of 20 buttons, an illuminated display panel, and an integrated loudspeaker, like the standard call station
• Call station with soft touch button
• Built-in alarm buttons and key switch for emergency use
• 15 freely programmable buttons
• Customization via built-in display and keys
• EN 54-16 system certification
Environmental directive compliance
- Safety EN 62368-1
- Immunity EN 50130-4
- Emissions EN 61000-6-3; ICES-003; FCC-47 part 15B class A
- Environment EN 50581
- Maritime EN 60945
Electrical
- CAN BUS port: 10, 20, or 62.5 kbit/s, 1 x RJ-45, max. length 1000 m
- Communications Systems - PVA-15ECS Emergency call station 3 | 4
- Maximum mic input level -21 dBu
- Maximum line input level +4 dBu
- Maximum NF output level +12 dBu
- Microphone
Nominal acoustic input level: 85 dBSPL
Frequency response: 250 Hz - 10 kHz (-10dB)
Signal to noise ratio: > 60dB